Steam Trap embedded in Pressure Reducing Valve.
Pressure Reducing Valve with Steam Trap.Feature
- It is very suitable to install at a place where drainage is easy to stay.
- Preventing the drainage to go on secondary side in the control devices.
- Preventing against the uncontrolled RP-6 by drainage at the beginning of steam blow.
- End connection for drainage side can be turned 90-degree, and easy to connect with pipe.
- Possible to add the Steam trap part to RP-6 already installed for sizes 15mm to 50mm.
RP-6BD
|
|
Dimensions
| Size | L | G | H | H1 | A | Cv | Weight(kg) |
| 15 | 190 | 135 | 155 | 72 | 1/2 | 1 | 10 |
| 20 | 190 | 135 | 155 | 72 | 1/2 | 2.5 | 10 |
| 25 | 150 | 190 | 160 | 77 | 1/2 | 4 | 11.5 |
| 32 | 180 | 151 | 182 | 88 | 3/4 | 6.5 | 14.5 |
| 40 | 180 | 151 | 182 | 88 | 3/4 | 9 | 15 |
| 50 | 200 | 166 | 187 | 98 | 3/4 | 16 | 18.5 |

Max. continual discharge amount.
| Pressure differential (MPa) | 0.05 | 0.1 | 0.2 | 0.3 | 0.4 | 0.6 | 0.8 | 1.0 |
| Discharge amount (l/h) | 100 | 160 | 260 | 340 | 400 | 500 | 550 | 590 |